top of page
SKU: SHS-7722779

Viessmann Vitodens 200-W B2HE-120 Gas Condensing Boiler, 120 MBH

$5,500.42 Regular Price
$3,987.25Sale Price

Buy more, save more: buy 4+, extra 15% off · Buy more, save more: buy 3, extra 10% off

Quantity

The Viessmann Vitodens 200-W B2HE-120 (7722779) is a wall-mounted, heat-only gas condensing boiler for homes and light commercial spaces. It modulates from 8.5 to 120 MBH on natural gas, reaches 95% AFUE and comes with an onboard 7 in. color touchscreen control.

Pairing a MatriX-Plus modulating cylinder burner with an Inox-Radial stainless heat exchanger, it delivers a Net AHRI rating of 98 MBH. Sound ranges from 34 dB at minimum to 59 dB at maximum fire, maximum condensate is 1.2 USG/h, and operation is possible up to 10,000 ft. NOx is below 20 ppm, meeting SCAQMD 1146.2, BAAQMD Reg. 9-6 and SJVAPCD 4308.

The direct-vent boiler uses a 3 in. (80 mm) flue with 5 in. (125 mm) coaxial air or 3 in. single pipe, with vent runs up to 180 ft. Heating supply/return is 3/4 in. NPTM, the DHW tank loop is 3/4 in. NPT and gas is 3/4 in. NPTF. An integral variable-speed boiler pump, DHW sensor and outdoor sensor simplify commissioning, and the touchscreen adds Wi-Fi and outdoor reset.

Highlights

  • 8.5-120 MBH input on natural gas; Net AHRI 98 MBH

  • 95% AFUE with Inox-Radial stainless-steel heat exchanger

  • Integral variable-speed boiler pump and 7 in. touchscreen control

  • Direct venting with runs up to 180 ft

  • Low-NOx under 20 ppm; built to CSA B51 and ASME Section IV

Specifications

Brand

Viessmann

Model

7722779

Input

8.5-120 MBH (NG)

Net AHRI

98 MBH

Efficiency

95% AFUE

Fuel

Natural gas

Burner

MatriX-Plus modulating cylinder

Heat exchanger

Stainless-steel Inox-Radial

Sound level

34-59 dB

Max condensate

1.2 USG/h

Venting

3 in. flue, 5 in. coaxial or 3 in. single pipe

Heating connections

3/4 in. NPTM

Gas connection

3/4 in. NPTF

Electrical

120 V, 60 Hz

Width

17.75 in.

Depth

19.75 in.

Weight

143 lb

Certifications

CSA B51, ASME Section IV, low-NOx

In the box

  • Pressure gauge

  • Installation fittings with 30 psig PRV

  • DHW sensor

  • 7 in. touchscreen control with outdoor sensor

  • Wall-mount bracket and hardware

  • Integral variable-speed boiler pump

Good to know

  • Gas-fired appliance: it must be installed, vented and commissioned by a qualified installer in line with local codes and the manufacturer's installation manual.

    bottom of page